Products
Contact Us
Telephone:+86 0391-8987988
Mobile:+8613598529809
Mailbox:liyao7979@163.com
Address: North of the next phase of Chengcun, Hongchang Sub-district Office, Boai County, Jiaozuo City, Henan Province

XHHV535-2TX Cable Fault Location System
Key words:
Products
and
the
power
voltage
cable
high-voltage
large-capacity
pulse
discharge
battery
impact
fault
XHHV535-2TX Cable Fault Location System
Cable Fault Location System
XHHV535-2TX
Location
Key words:
XHHV535-2TX Cable Fault Location System
Classification:
Product description
Product Overview
This device is a five-in-one cable fault location system that integrates a cable fault tester, a path meter transmitting module, a high-voltage pulse generator, a large-capacity battery pack, and a positioning instrument. It is used to detect the main insulation fault of power cables with voltage levels of 35kV and below, calibrate the length, and accurately detect the buried direction and depth.
Core functions and components:
Cable fault tester: integrated operating software (single-chip microcomputer control, touch operation), large-capacity lithium battery, independent power supply and anti-interference, stable and convenient.
Cable path meter: built-in battery power supply, supports convenient operation, including overload protection and amplitude adjustment functions.
High-voltage pulse generator: supports battery/AC220V power supply, has DC withstand voltage, single/cycle pulse output and signal feedback functions, with zero protection and automatic discharge when shut down.
Large-capacity battery pack (12.6V): Power supply for high-voltage pulse generator and path meter.
Cable fault positioning instrument: used for accurate positioning of cable fault points.
Scope of application: Covers power cables, high-frequency coaxial cables, street light cables, and underground wires of different cross-sections and media, and can detect low-resistance short circuit/open circuit, high-resistance leakage/flashover and other faults.
Technical compliance: Complies with GB/T 18268.1, DL/T 849.1-2019 (flash tester), DL/T 849.2-2019 (point meter), DL/T 849.3-2019 (path meter), JJF1042-2020 and other standards.
Product Features
★ With over-current, over-voltage, over-heating automatic protection function;
★ Super short-circuit protection function, which can make the high-voltage output directly short-circuit to the ground;
★ With current and voltage dual 1.5-level pointer meter display, intuitive and clear; whether the fault point is fully discharged is clear at a glance, and the discharge process is reflected in real time;
★ With zero-position start protection, it is safer and more reliable;
★ High-voltage pulse output is uniform and controllable;
★ High-voltage side voltage measurement, real-time and accurate;
★ Unique high-voltage measurement design, when stopped, it will automatically discharge the internal capacitor of the equipment;
★ The discharge time can choose two modes: timing and manual;
★ With DC withstand voltage function;
★ High-precision test cable fault sampling waveform module is installed inside;
★ Humanized design trolley, easy to move;
Technical parameters
★ Impact high voltage: 0~32kV optional
★ High-voltage voltage division: voltage accuracy 1.5 level
★ Built-in capacitor: 2μF
★ Output voltage polarity: negative polarity
★ Discharge power: 1024J
★ Impact time: automatic impact for about 5 seconds, manual impact for any control time
★ Impact power: 2000W
★ Overcurrent protection: 10A (more than 3 seconds)
★ Volume: 534L×444W×805H
★ Weight: no more than 130kg
★ Working power: AC 220V±10% 50Hz±2Hz/built-in 100AH power supply
★ Ambient temperature: -20~+50℃